When it comes to commercial building design and exterior envelope performance, one crucial element is frequently at the center of water intrusion failures: sealants. In the facade consulting industry, sealant selection and application are among the most common root causes of building envelope defects we encounter during forensic investigations. At Facade Consultants, we have investigated sealant failures in hundreds of commercial buildings from high-rise office towers to institutional campuses.
Improper sealant specification, poor surface preparation, and inadequate quality control during application are responsible for a significant percentage of the facade failures we document. This guide will help building owners, property managers, architects, and attorneys understand how commercial sealants perform, why they fail, and when a forensic investigation is warranted.

Applicable Industry Standards
All sealant evaluation, testing, and forensic analysis referenced in this guide align with the following ASTM International standards. These standards form the basis for expert opinions in construction defect litigation:
The Three Types of Facade Leaks
When analyzing building performance, we look for three specific types of intrusion. While a layperson might call them leaks, industry professionals use specific terminology to accurately diagnose the issue.
- Air Infiltration: Uncontrolled air movement through the building envelope impacts energy efficiency, HVAC load calculations, and occupant comfort. Testing is performed per ASTM E783 (field) and ASTM E283 (laboratory). In commercial buildings, excessive air infiltration can add tens of thousands of dollars annually to operating costs.
- Water Penetration: The most structurally damaging type of leak, often leading to concealed corrosion, mold growth, deterioration of insulation, and progressive structural damage. Water intrusion testing follows ASTM E1105 (field) and AAMA 501.2 protocols. This is the failure mode most commonly at issue in construction defect litigation.
- Acoustical Leakage: Sound transmission through the building envelope can severely impact occupant comfort and regulatory compliance in urban, healthcare, and institutional environments. STC (Sound Transmission Class) ratings are evaluated in accordance with ASTM E90.

Diagnosing Sealant Failures: Why Leaks Happen
“Where does it leak?” is the first question a facade consultant asks. But identifying the location is only the beginning. A proper forensic investigation determines the root cause of failure, which is essential for both effective repair and for establishing liability in construction defect cases.
Sealant failures generally fall into specific categories, each with a technical designation:
Material Application Failures
- Voids: Holes or gaps in the sealant bead caused by improper gunning technique, inadequate tooling, or failure to fill the joint cavity. Voids are a direct violation of ASTM C1193 application guidelines and constitute a workmanship defect.
- Cohesive Failure: The sealant tears or splits down its center, indicating the material could not accommodate the joint movement. This may result from specifying a sealant with insufficient movement capability for the joint design, or from joints that exceed the sealant manufacturer’s maximum width-to-depth ratio.
- Adhesive Failure: The sealant separates cleanly from the substrate, indicating poor surface preparation (contamination, moisture, or lack of primer) or chemical incompatibility between the sealant and the substrate. Per ASTM C1521, field pull tests can definitively identify adhesive failure.

Structural and Assembly Issues
- Joinery Failure: Leaks at frame corners often indicate inadequate corner sealing during fabrication or assembly, rather than a sealant issue.
- Sill Termination Failure: Deficiencies at the end dams where water should be captured and diverted. These failures are particularly common in window wall and curtain wall systems and frequently require forensic water testing to isolate.
- Poor Adjustment: Sash components that do not compress weatherstripping or gaskets correctly, resulting in air and water leakage. This is an installation defect that may be concealed behind trim or cladding.
Sealant Testing Methodology: How We Investigate
Our forensic sealant investigations follow a systematic, standards-based protocol designed to produce defensible findings for both remediation and litigation:

Sealant Selection: The Right Product for the Application
The fundamental rule of sealant performance is straightforward: use the correct sealant for the application. In our forensic practice, we consistently find that specifying the wrong chemical composition for the environment and substrate is a leading cause of premature facade failure and a frequent basis for construction defect claims.
For Interior Applications Only
These sealants are generally easier to apply and paint but lack the durability required for exterior exposure to UV, thermal cycling, and wind-driven rain:
- Latex
- Acrylic Latex
- Siliconized Latex
For Exterior or Interior Applications
These high-performance materials are designed to withstand UV exposure, thermal movement, and precipitation in commercial building envelopes. Selection must comply with ASTM C920 classifications:
- Silicone: Excellent UV resistance, high movement capability (±50% for Class 50), and superior longevity. Non-paintable in most formulations. Widely specified for curtain wall and structural glazing applications.
- Polyurethane: Outstanding adhesion and abrasion resistance with good paintability. Often specified for precast concrete, masonry, and metal panel joints. Movement capability is typically ±25%.
- Acrylic Terpolymer: A versatile option offering good adhesion to a wide range of substrates, including EIFS, concrete, and wood. Lower movement capability than silicone.

For Insulated Glass Unit (IGU) Seals
The primary and secondary seals for insulated glass units require specific chemical compatibility to maintain the hermetic seal and structural integrity of the unit:
- Butyl: Used as a primary (inner) seal for its extremely low moisture vapor and gas permeability. Critical for maintaining the argon or krypton gas fill.
- Silicone: Used for structural strength as the secondary (outer) seal, providing UV resistance and structural bonding to the spacer assembly.
- Polysulfide: A traditional secondary seal choice offering good solvent resistance, though increasingly replaced by silicone in modern IGU fabrication.

Sealant Failure as Evidence in Construction Defect Cases
Sealant failures are among the most common and most provable defects in construction defect litigation. Because sealant application is governed by well-defined ASTM standards and manufacturer installation guidelines, deviations from those standards can be objectively documented and presented as evidence of negligent workmanship or defective design.
Common Litigation Scenarios We EncounterWhat Attorneys Should Know
Sealant defect cases are uniquely well-suited for expert testimony because the applicable standards are specific and measurable. ASTM C1521 pull tests produce quantitative adhesion data. ASTM E1105 water testing produces pass/fail results at defined test pressures. Laboratory analysis can confirm whether the installed sealant matches the specified product. This objective evidence differentiates sealant cases from more subjective construction disputes.
The Cost of Sealant Failure: Why Prevention Matters
The economic consequences of sealant failure in commercial buildings extend far beyond the cost of re-caulking. Based on our experience investigating hundreds of commercial building failures, the following cost multipliers are typical:
| Failure Consequence | Estimated Cost Impact |
|---|---|
| Sealant replacement (proactive) | $3–$8 per linear foot |
| Water damage remediation (reactive) | $50–$200+ per linear foot of affected area |
| Mold remediation (interior walls) | $10,000–$100,000+ per affected zone |
| Structural steel corrosion repair | $50,000–$500,000+ depending on extent |
| Litigation & expert witness costs | $100,000–$1M+ for complex facade cases |
| Business interruption / tenant displacement | Highly variable; often exceeds repair costs |
Key takeaway: Proactive sealant maintenance costs a fraction of reactive remediation. A professional sealant survey by a qualified facade consultant can identify deteriorating conditions before water intrusion causes concealed damage and before the statute of repose limits legal options.
When to Engage a Facade Consultant for Sealant IssuesYou should consider engaging Facade Consultants when you encounter any of the following conditions:
Bonus Content

Schedule a Consultation
Contact Facade Consultants to discuss your concerns about your building’s sealant performance. Whether you are a building owner seeking a forensic investigation, an architect needing peer review, or an attorney requiring expert witness services, our team provides objective, standards-based analysis. Call us at (847) 674-8444 or visit facadeconsultants.com/contact to schedule a consultation.